Selection Guide for Electric Wire Size
FLUID POWER - Design Data Sheet 11
Two Factors to be Considered
When choosing the conductor size for electrical wiring, there
are TWO important factors which must be considered, and these are:
(1), the safe current-carrying capacity without overheating, and
(2), keeping the voltage loss to an acceptable minimum.
On short wiring runs, say up to 20 feet, the voltage loss is
usually negligible, and need not be considered. Wire size should be
selected solely for its current capacity as shown in Chart 1.
On longer runs, say several hundred feet or more, the voltage
loss may be excessive even though the wire has been selected to
carry the current without overheating. In this case, a wire of
larger diameter should be used which will keep the voltage loss to
a selected minimum. Voltage loss per 1000 feet is shown in Chart 2
according to wire size.
Permissible Voltage Loss
There is a voltage loss on any wiring run, and the designer must
decide how much can be tolerated without seriously affecting
performance. He must select a wire size which will keep the loss
within the acceptable limit. Electric motors generally should not
be operated at full load on less than 90% of nameplate voltage.
When deciding on acceptable voltage loss in the wiring, the
minimum voltage available from the power line at certain periods of
the day must be considered. For example, a motor rated at 230 volts
should not be run at full load at less than 208 volts (10% less
than nameplate rating). If line voltage may sometimes drop as low
as 220 volts, the wiring should be designed for no more than 12
volts loss.
A rule-of-thumb is to design the wiring of sufficient size so
the voltage drop will not exceed 5% of the input voltage.
Chart 1 - Wire Ampacity for Short Wiring
Runs
"Ampacity" is an abbreviation for ampere capacity. This chart is
for short wiring runs of less than 20 feet. Values in the chart are
taken from the NEC (National Electrical Code) for wire sizes of No.
14 and larger wire. The current capacity depends on the type of
insulation and on how the wire is installed - whether confined in a
raceway or exposed to the open air. The chart is based on the use
of low temperature insulation (140°F). Wire with high temperature
insulation will carry higher current without damage to the
insulation. For capacity of larger wires, consult the NEC code.
(Figures in the body of this chart are recommended maximum
current ratings, in amperes)
| Wire Size, B & S |
18 |
16 |
14 |
12 |
10 |
8 |
6 |
4 |
3 |
2 |
1 |
0 |
00 |
000 |
0000 |
| In Raceway or Cable |
6 |
9 |
15 |
20 |
30 |
40 |
55 |
70 |
80 |
95 |
110 |
125 |
145 |
165 |
195 |
| In Open Air |
8 |
12 |
20 |
25 |
40 |
55 |
80 |
105 |
120 |
140 |
165 |
195 |
225 |
260 |
300 |
Chart 2 - Voltage Loss on Long Wiring Runs
The chart is for long runs, several hundred feet or longer.
Before using the chart, the operating conditions must be determined
or decided on, which include the following:
(1). Current draw on the line must be determined.
(2). The amount of voltage loss which can be tolerated must be
decided on.
(3). The length of wiring run must be measured or calculated
using the sum of outgoing and return wire lengths.
On 3-phase devices such as electric motors, each of the three
main wires must carry the current shown on the motor nameplate.
However, the length of wiring run is the sum of two (not all three)
connecting wires.
Read across the top of the chart to find the column which
matches the amperage rating of the load. Figures in this column
show voltage losses per 1000 feet of wire length, the sum of
outgoing plus return. If, for example, the total wire length is 250
feet, losses would be 1/4th chart values, etc.
Wire
Size
B & S |
Current Flow,
Amperes |
| 5 |
10 |
15 |
20 |
25 |
30 |
40 |
50 |
60 |
70 |
80 |
90 |
100 |
| 18 |
32.55 |
65.10 |
97.65 |
130.2 |
162.8 |
195.3 |
260.4 |
325.5 |
390.6 |
455.7 |
520.8 |
585.9 |
651.0 |
| 16 |
20.47 |
40.94 |
61.41 |
81.88 |
102.4 |
122.8 |
163.8 |
204.7 |
245.6 |
286.6 |
327.5 |
368.5 |
409.4 |
| 14 |
12.88 |
25.75 |
38.63 |
51.50 |
64.38 |
77.25 |
103.0 |
128.8 |
154.5 |
180.3 |
206.0 |
231.8 |
257.5 |
| 12 |
8.095 |
16.19 |
24.28 |
32.38 |
40.48 |
48.57 |
64.76 |
80.95 |
97.14 |
113.3 |
129.5 |
145.7 |
161.9 |
| 10 |
5.090 |
10.18 |
15.27 |
20.36 |
25.45 |
30.54 |
40.72 |
50.90 |
61.08 |
71.26 |
81.44 |
91.62 |
101.8 |
| 8 |
3.203 |
6.405 |
9.608 |
12.81 |
16.02 |
19.22 |
25.62 |
32.03 |
38.43 |
44.84 |
51.24 |
57.65 |
64.05 |
| 6 |
2.014 |
4.028 |
6.042 |
8.056 |
10.07 |
12.08 |
16.11 |
20.14 |
24.18 |
28.21 |
32.24 |
36.27 |
40.30 |
| 4 |
1.267 |
2.533 |
3.800 |
5.068 |
6.335 |
7.602 |
10.14 |
12.68 |
15.22 |
17.75 |
20.29 |
22.82 |
25.36 |
| 3 |
1.005 |
2.009 |
3.014 |
4.020 |
5.025 |
6.030 |
8.040 |
10.05 |
12.07 |
14.08 |
16.09 |
18.10 |
20.11 |
| 2 |
0.796 |
1.593 |
2.390 |
3.184 |
3.980 |
4.776 |
6.368 |
7.960 |
9.552 |
11.14 |
12.74 |
14.33 |
15.92 |
| 1 |
0.632 |
1.264 |
1.896 |
2.528 |
3.160 |
3.792 |
5.056 |
6.320 |
7.584 |
8.848 |
10.11 |
11.38 |
12.64 |
| 0 |
0.501 |
1.002 |
1.503 |
2.004 |
2.505 |
3.006 |
4.008 |
5.010 |
6.012 |
7.014 |
8.016 |
9.018 |
10.02 |
| 00 |
0.398 |
0.796 |
1.193 |
1.592 |
1.990 |
2.388 |
3.184 |
3.980 |
4.776 |
5.572 |
6.368 |
7.164 |
7.960 |
| 000 |
0.315 |
0.630 |
0.945 |
1.260 |
1.575 |
1.890 |
2.520 |
3.150 |
3.780 |
4.410 |
5.040 |
5.670 |
6.300 |
| 0000 |
0.250 |
0.500 |
0.750 |
1.000 |
1.250 |
1.500 |
2.000 |
2.500 |
3.000 |
3.500 |
4.000 |
4.500 |
5.000 |
Chart 2 - Figures in body of chart show voltage loss per 1000
feet of wiring run.
Safety Unloading of Accumulators

Figure 1. An accumulator contains a highly
compressed gas and can be potentially hazardous in a hydraulic
system. It may retain its charge long after the system has been
shut down. Service personnel may not be aware of the presence of an
accumulator, and could be injured by high pressure oil if a fitting
is loosened. A safety circuit should be used which will
automatically discharge the accumulator when the system is shut
down or the electric motor is stopped.
Solenoid Valve B, which is a 2-way, normally open type, will
bleed off the accumulator every time the electric motor is stopped.
It can be a miniature size, 1/8 or 1/4", single solenoid type.
Solenoid A is part of the system relief valve which is a pilot
operated relief with solenoid dump, which unloads the pump when the
accumulator comes up to pressure.

Figure 2. Solenoid Valve B is wired into the
electric motor circuit, and opens to bleed off the accumulator when
the electric motor is stopped.
Solenoid A is wired through a pressure switch. When the
accumulator comes up to full charge, the pressure switch contacts
open, breaking the circuit to Solenoid A and allowing the pump to
dump through the relief valve.
The solenoids receive electrical power through a control
transformer which takes power from one phase and steps the voltage
down if necessary.
|
The National Electrical Code (NEC) has been adopted and is
published by several agencies. Copies may be purchased by writing
to the American National Standards Institute, Inc. (ANSI), 1430
Broadway, New York, N.Y. 10018, or to National Fire Protection
Association (NFPA), 60 Batterymarch St., Boston, MA 02110. An
amplified version with explanations accompanying the text is
published by McGraw-Hill and may be ordered through any book